Overall Chilled Water System Energy Consumption Modeling and Optimization

dc.contributor.authorTrautman, Neal
dc.contributor.authorRazban, Ali
dc.contributor.authorChen, Jie
dc.contributor.departmentMechanical and Energy Engineering, School of Engineering and Technologyen_US
dc.date.accessioned2022-01-24T19:32:28Z
dc.date.available2022-01-24T19:32:28Z
dc.date.issued2021-10
dc.description.abstractThe emergence of increasingly affordable variable-speed drive technology has changed the approach used to control chilled water systems equipped with these drives. The purpose of this research was to develop an integrated chilled water modeling technique that can determine the optimal system setpoints and estimate the energy saving potential of chiller system. The chiller system equipped with Variable Frequency Drives (VFDs) on cooling tower fans and condenser water pumps. To accomplish the objective, physical component models of the centrifugal chiller, cooling tower and condenser water pump were established with the goal of incorporating the system’s condenser water flow rate and cooling tower fan speeds as optimization variables. Furthermore, a cooling load prediction algorithm was developed using a multiple non-linear regression model to approximate the building’s cooling load subject to a range of environmental conditions. The inputs and outputs of the individual component models were linked to estimate how adjusting the cooling tower fan and condenser water pump speed would influence the system’s comprehensive performance. The overall system model was then optimized using a generalized reduced gradient optimization algorithm to determine the potential energy savings through speed control with VFDs and to ascertain a control logic strategy for the building automation system to operate the heating and cooling system. A case-study was performed on a single chiller system at a museum and the model was calibrated according to logged data collected over four months. Results showed that for the system analyzed, the energy saving of optimizing the cooling tower fan system was found to be 12–15%, while the energy saving potential of optimizing the condenser water pump with the cooling tower fan was negligible. Additionally, comparing different cooling tower fan control strategies showed that a wet-bulb approach-based cooling tower control strategy was shown to have the highest correlation to the optimized fan speed with an R2 of 0.924.en_US
dc.eprint.versionAuthor's manuscripten_US
dc.identifier.citationTrautman, N., Razban, A., & Chen, J. (2021). Overall chilled water system energy consumption modeling and optimization. Applied Energy, 299, 117166. https://doi.org/10.1016/j.apenergy.2021.117166en_US
dc.identifier.urihttps://hdl.handle.net/1805/27552
dc.language.isoenen_US
dc.publisherElsevieren_US
dc.relation.isversionof10.1016/j.apenergy.2021.117166en_US
dc.relation.journalApplied Energyen_US
dc.rightsPublisher Policyen_US
dc.sourceAuthoren_US
dc.subjectchilled water systemen_US
dc.subjectvariable speed driveen_US
dc.subjectcondenser water systemen_US
dc.titleOverall Chilled Water System Energy Consumption Modeling and Optimizationen_US
dc.typeArticleen_US
Files
Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Trautman_2021_overall.pdf
Size:
1.95 MB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.99 KB
Format:
Item-specific license agreed upon to submission
Description: